PVI 1000

The Switch photovoltaic inverters (PVI) are specifically designed for utility-grade solar applications to optimize solar power harvesting and LCOE (Levelized Cost Of Energy) in central inverter megawatt-scale photovoltaic power plants.

Each system component is chosen to maximize system performance, efficiency and uptime for optimum overall power generation and plant revenue throughout the lifetime of the power plant.

The Switch PVI design offers up to 98% efficiency, and total current harmonic distortion is typically less than 3%.

Features

Advantages

Rugged IP66/Nema 4 enclosure Totally sealed and self-contained inverter assembly, resilient for outdoor installation in harsh ambient conditions, eliminating costs of additional housing or cooling
   
One shipping unit Complete, compact unit shipped in one single “plug and produce” assembly
   
Integrated liquid-cooling system Self-contained liquid-cooling system, factory filled and tested, with no need for onsite piping or plumbing, simplifies operation, maintenance and installation
   
Grid compliance and support Field-verified compliance with evolving utility needs that includes fault ride-through (FRT) functionality; continuous active and reactive power stabilizes grid voltage and frequency during grid disturbances, varying voltage fluctuation and electrical system fault conditions
   
Power saving and standby mode Energy-efficient temperature management system minimizes power consumption and tare losses
   
Built-in diagnostics Robust, built-in features for monitoring, diagnosing, data logging and reporting ensure optimum performance and system availability


Specifications

The Switch PVIs comply with the latest national and international standards set for grid-tied operation, safety and electromagnetic compatibility, including UL508C, UL1741, NEC690, IEEE 929, IEC61683, IEC61727, EN50081, EN50082, EN61000 and FERC661A.

  PVI 1000
Nominal DC power rating [kW] 1000
(at 45 °C and nominal AC voltage)
Max. input voltage [Vdc] 1000
Max. power point tracking (MPPT)
input voltage range [Vdc]
550 – 900
Number of DC feeder landings 12+/12-
Array configuration Positive or negative leg grounded, or floating
AC voltage range [Vrms] 350 – 450
(nominal: 400)
Nominal AC frequency [Hz] 50/60
Max. AC line current [Arms] 1500
AC current distortion [%] <3 THD
Max. efficiency [%] 98
Power factor [cos Φ] 0.85 leading/0.85 lagging
Tare losses [W] <75
Cooling Self-contained liquid
Operating ambient temperature [°C] Up to +50
Enclosure rating
  Cooling section
IP65 (optional: IP66)/NEMA 4
IP54/NEMA 3R
Relative humidity [%] <100 with dehumidifier
Elevation [m] 1000 at full power/2000 with de-rating
Audible noise [dBA] <70
Size (length x width x height) [mm] 3000 x 1200 x 2400
Weight [kg] 400


Technical drawings

An outdoor megawatt-sized “plug and produce” building block with fully integrated liquid cooling and market-leading footprint.

The Switch - Photovoltaic inverters

Version 11.0, 02/2012 - We reserve the right to modify the information above at any time without notice.

The Switch - Photovoltaic inverter

Download The Switch photovoltaic inverter datasheet as pdf-document


Want to know more?

Contact form

Telephone exchange
+358 20 7838 200

Technical 24h support line
+358 40 0922 113